Automatic air vents and separators (micro bubble, dirt, combined)

Comprehensive range of products for venting and separation of micro bubbles, sludge and magnetite in heating, solar and cooling water systems.

The diversity of the applications as well as their modular construction is unique. The helistill separator makes these products incredibly efficient.

Technical description

  • Application: Heating, solar and chilled water systems
  • Media: Non-aggressive and non-toxic system media. Addition of antifreeze agent up to 50%.
  • Pressure: Max. admissible pressure, PS: 10 bar. Min. admissible pressure, PSmin: 0 bar
  • Temperature: Max. admissible temperature, TS: 110 °C; Min. admissible temperature, TSmin: -10 °C; Zeparo ZUTS, ZUVS, ZUVLS solar: Max. admissible temperature, TS: 160 °C; Min. admissible temperature, TSmin: -10 °C
  • Material: Brass
  • Transportation and storage: In frostless, dry places